Combination Controls CG 1-3

Compact gas control systems with filter or dirt trap, governor, integrated pressure switch, two class A solenoid valves for safeguarding and control of atmospheric burners, forced draught burners and draught-assisted boilers on heating systems up to 400 kW, electrical connection with standard plug and socket, EC type tested and certified.

  • Size: 1 to 3
  • DN: 10 to 40
  • Connection: thread
  • PE: 5 to 100 mbar
  • Δp: max. 50 mbar
  • various controller types:
  • CG..D: governor with adjustable start gas stage
  • CG..Z: governor with adjustable start gas stage and two-stage operation
  • CG..V: variable air/gas ratio control with adjustable air/gas ratio
  • mains voltage: 24 V AC/DC, 120 V AC or 220/240 V AC
  • two class A solenoid valves
  • The following versions are available: combination controls with flow adjustment

CG 115..D
CG 115..D
CG 225..Z
CG 225..Z
CG 340..V
CG 340..V